Process Image Reference

All offsets are relative to the separately addressed submodule. Multi-byte numbers use big-endian encoding; Real uses IEEE-754. UUID fields are fixed Char arrays containing the canonical ASCII UUID; an all-zero field represents the NIL UUID. AuxVariable strings use the encoding in AuxVariable Types.

Table: Core Input Relative Offsets​

Relative byteUDT field and S7 typeMeaning
0..35current_flow_uuid: Array[0..35] of Charcurrent Flow UUID
36..71current_tool_uuid: Array[0..35] of Charcurrent tool UUID
72..75current_global_speed: UDIntpercentage
76..77last_error_code: UIntlatest backend error code
78..79flow_state: UIntflow_state
80..81robot_state: UIntrobot_state
82..83safety_state: UIntsafety_state
84..85status.ack_seq: UIntaccepted sequence
86..87status.last_req_seq: UIntresult sequence
88..89status.last_req_status: UIntrequest status

All named Core Input flags are Bool values.

Relative bitUDT field
90.0flags.operational
90.1flags.robot_in_home_position
90.2flags.teach_mode
90.3flags.safety_auto_mode
90.4flags.safety_manual_mode
90.5flags.flow_running
90.6flags.flow_paused
90.7flags.flow_ready_to_start
91.0flags.brakes_closed
91.1flags.system_alarm_error
91.2flags.emergency_stop_triggered
91.3flags.hand_guiding
91.4flags.control_external_active
91.5flags.control_local_active
91.6flags.enabling_device_pressed
91.7reserved

The authority flags report the selected Single Point of Control owner; see Single Point of Control. enabling_device_pressed mirrors the physical SCU enabling switch. It is false when detailed SCU status is unavailable or invalid. It does not grant control authority. emergency_stop_triggered indicates a safe-stop state, including safe stops other than a physical emergency stop. These cyclic status flags are diagnostic information, not safety-rated signals.

Table: Core Output Relative Offsets​

Relative byteUDT field and S7 typeUsed by
0..35requested_flow_uuid: Array[0..35] of CharSTART_FLOW
36..71requested_tool_uuid: Array[0..35] of CharSET_TOOL
72..75requested_global_speed: UDIntSET_GLOBAL_SPEED
76..77command.cmd_id: UIntcmd_id
78..79command.cmd_seq: UIntcommand sequence
80..81flags: two-byte bit fieldcommand flags
82requested_operation_mode: USIntlegacy field name; unused, write zero
83pad_byte: Bytealways write zero
Relative bitUDT fieldUsed by
80.0flags.brakes_closedSET_BRAKES
80.1flags.acknowledge_errorlegacy field; unused, write false
80.2flags.hand_guidingSET_HAND_GUIDING
80.3..81.7reservedwrite zero

pad_byte is explicit protocol data that keeps the GSDML and imported UDT at 84 bytes; it is not an implicit Profinet alignment byte.

Table: Optional Base Submodule Relative Offsets​

Each table starts at byte zero of its separately addressed submodule. Input contains current values; Output contains requested values.

Payload IO Submodule: current / requested payload​

Both directions use RobCo_Payload.

Relative byteUDT fieldS7 type
0massReal
4com_xReal
8com_yReal
12com_zReal
16ixxReal
20ixyReal
24ixzReal
28iyyReal
32iyzReal
36izzReal

The inertia fields are the upper triangle of the symmetric tensor, ordered ixx, ixy, ixz, iyy, iyz, izz, in kg*m^2.

CartesianPose IO Submodule: current / requested TCP pose​

Both directions use RobCo_CartesianPose.

Relative byteUDT fieldS7 type
0position_xReal
4position_yReal
8position_zReal
12orientation_rzReal
16orientation_ryReal
20orientation_rxReal

JointPose IO Submodule: current / requested joint pose​

Both directions use RobCo_JointPose.

Relative byteUDT fieldS7 type
0joint_angle_1Real
4joint_angle_2Real
8joint_angle_3Real
12joint_angle_4Real
16joint_angle_5Real
20joint_angle_6Real
24joint_angle_7Real
28joint_angle_8Real